Overview
The Calejo Control Adapter is a multi-protocol integration adapter designed for municipal wastewater pump stations. It translates optimized pump control plans from Calejo Optimize into real-time control signals while maintaining comprehensive safety and security compliance.
Key Design Principles:
- Safety First: Multi-layer safety architecture with failsafe mechanisms
- Security by Design: Built-in security controls compliant with industrial standards
- Protocol Agnostic: Support for multiple industrial protocols simultaneously
- High Availability: Redundant components and health monitoring
- Transparent Operations: Comprehensive audit logging and monitoring
System Architecture
High-Level Architecture
┌─────────────────────────────────────────────────────────┐
│ Calejo Optimize Container (Existing) │
│ - Optimization Engine │
│ - PostgreSQL Database (pump plans) │
└─────────────────────────────────────────────────────────┘
↓
┌─────────────────────────────────────────────────────────┐
│ Calejo Control Adapter (IMPLEMENTED) │
│ │
│ ┌────────────────────────────────────────────────┐ │
│ │ Core Components: │ │
│ │ 1. Auto-Discovery Module ✅ │ │
│ │ 2. Safety Framework ✅ │ │
│ │ 3. Emergency Stop Manager ✅ │ │
│ │ 4. Optimization Plan Manager ✅ │ │
│ │ 5. Setpoint Manager ✅ │ │
│ │ 6. Database Watchdog ✅ │ │
│ │ 7. Alert Manager ✅ │ │
│ │ 8. Multi-Protocol Server ✅ │ │
│ │ - OPC UA Server │ │
│ │ - Modbus TCP Server │ │
│ │ - REST API │ │
│ └────────────────────────────────────────────────┘ │
└─────────────────────────────────────────────────────────┘
↓
(Multiple Protocols)
↓
┌─────────────────┼─────────────────┐
↓ ↓ ↓
Siemens WinCC Schneider EcoStruxure Rockwell FactoryTalk
Component Architecture
Core Components
1. Auto-Discovery Module (src/core/auto_discovery.py)
- Purpose: Automatically discovers pump stations and pumps from database
- Features:
- Dynamic discovery of pump configurations
- Periodic refresh of station information
- Integration with safety framework
- Configuration: Refresh interval configurable via settings
2. Safety Framework (src/core/safety.py)
- Purpose: Multi-layer safety enforcement for all setpoints
- Three-Layer Architecture:
- Layer 1: Physical Hard Limits (PLC/VFD) - 15-55 Hz
- Layer 2: Station Safety Limits (Database) - 20-50 Hz (enforced here)
- Layer 3: Optimization Constraints (Calejo Optimize) - 25-45 Hz
- Features:
- Rate of change limiting
- Emergency stop integration
- Failsafe mode activation
3. Emergency Stop Manager (src/core/emergency_stop.py)
- Purpose: Manual override capability for emergency situations
- Features:
- Station-level and pump-level emergency stops
- Automatic setpoint override to 0 Hz
- Manual reset capability
- Audit logging of all emergency operations
4. Optimization Plan Manager (src/core/optimization_manager.py)
- Purpose: Manages optimization plans from Calejo Optimize
- Features:
- Periodic polling of optimization database
- Plan validation and safety checks
- Integration with setpoint manager
- Plan execution monitoring
5. Setpoint Manager (src/core/setpoint_manager.py)
- Purpose: Calculates and manages real-time setpoints
- Calculator Types:
DIRECT_SPEED: Direct speed controlLEVEL_CONTROLLED: Level-based control with feedbackPOWER_CONTROLLED: Power-based control with feedback
- Features:
- Real-time setpoint calculation
- Integration with safety framework
- Performance monitoring
Security Components
6. Security Manager (src/core/security.py)
- Purpose: Unified security management
- Components:
- Authentication Manager: JWT-based authentication with bcrypt password hashing
- Authorization Manager: Role-based access control (RBAC)
- Security Manager: Coordination of authentication and authorization
- User Roles:
READ_ONLY: Read-only access to system statusOPERATOR: Basic operational controls including emergency stopENGINEER: Configuration and safety limit managementADMINISTRATOR: Full system access including user management
7. Compliance Audit Logger (src/core/compliance_audit.py)
- Purpose: Comprehensive audit logging for regulatory compliance
- Supported Standards:
- IEC 62443 (Industrial Automation and Control Systems Security)
- ISO 27001 (Information Security Management)
- NIS2 Directive (Network and Information Systems Security)
- Features:
- Immutable audit trail
- Event categorization by severity
- Compliance reporting
- Database and structured logging
8. TLS Manager (src/core/tls_manager.py)
- Purpose: Certificate-based encryption management
- Features:
- Certificate generation and rotation
- TLS/SSL configuration
- Certificate validation
- Secure communication channels
Protocol Servers
9. OPC UA Server (src/protocols/opcua_server.py)
- Purpose: Industrial automation protocol support
- Features:
- OPC UA 1.04 compliant server
- Node caching for performance
- Security policy support
- Certificate-based authentication
- Endpoints:
opc.tcp://0.0.0.0:4840
10. Modbus TCP Server (src/protocols/modbus_server.py)
- Purpose: Legacy industrial protocol support
- Features:
- Modbus TCP protocol implementation
- Connection pooling
- Industrial security features
- High-performance data access
- Port: 502
11. REST API Server (src/protocols/rest_api.py)
- Purpose: Modern web API for integration
- Features:
- OpenAPI documentation
- Response caching
- Compression support
- Rate limiting
- Port: 8080
Monitoring Components
12. Database Watchdog (src/monitoring/watchdog.py)
- Purpose: Ensures database connectivity and failsafe operation
- Features:
- Periodic health checks
- Automatic failsafe activation
- Alert generation on connectivity loss
- Graceful degradation
13. Alert Manager (src/monitoring/alerts.py)
- Purpose: Comprehensive alerting system
- Features:
- Multi-channel notifications (email, SMS, webhook)
- Alert escalation
- Alert history and management
- Integration with audit system
14. Health Monitor (src/monitoring/health_monitor.py)
- Purpose: System health monitoring and metrics
- Features:
- Component health status
- Performance metrics
- Resource utilization
- External health check endpoints
Data Flow Architecture
Setpoint Calculation Flow
1. Optimization Plan Polling
↓
2. Plan Validation & Safety Check
↓
3. Setpoint Calculation
↓
4. Safety Limit Enforcement
↓
5. Protocol Server Distribution
↓
6. SCADA System Integration
Safety Enforcement Flow
1. Proposed Setpoint
↓
2. Emergency Stop Check (Highest Priority)
↓
3. Hard Limit Enforcement
↓
4. Rate of Change Limiting
↓
5. Final Setpoint Validation
↓
6. Protocol Server Delivery
Security Architecture
Authentication & Authorization
- JWT-based Authentication: Secure token-based authentication
- Role-Based Access Control: Granular permissions per user role
- Certificate Authentication: For industrial protocol security
- Session Management: Secure session handling with timeout
Encryption & Communication Security
- TLS/SSL Encryption: All external communications
- Certificate Management: Automated certificate rotation
- Secure Protocols: Industry-standard security protocols
- Network Segmentation: Zone-based security model
Audit & Compliance
- Comprehensive Logging: All security-relevant events
- Immutable Audit Trail: Tamper-resistant logging
- Compliance Reporting: Automated compliance reports
- Security Monitoring: Real-time security event monitoring
Deployment Architecture
Container Architecture
┌─────────────────────────────────────────────────────────┐
│ Calejo Control Adapter Container │
│ │
│ ┌─────────────────┐ ┌─────────────────┐ │
│ │ OPC UA Server │ │ Modbus Server │ │
│ │ Port: 4840 │ │ Port: 502 │ │
│ └─────────────────┘ └─────────────────┘ │
│ │
│ ┌─────────────────┐ ┌─────────────────┐ │
│ │ REST API │ │ Health Monitor │ │
│ │ Port: 8080 │ │ Port: 8081 │ │
│ └─────────────────┘ └─────────────────┘ │
│ │
│ ┌─────────────────────────────────────────────────┐ │
│ │ Core Application Components │ │
│ │ - Safety Framework │ │
│ │ - Security Layer │ │
│ │ - Monitoring & Alerting │ │
│ └─────────────────────────────────────────────────┘ │
└─────────────────────────────────────────────────────────┘
High Availability Features
- Database Connection Pooling: Optimized database connectivity
- Component Health Monitoring: Continuous health checks
- Graceful Degradation: Failsafe operation on component failure
- Automatic Recovery: Self-healing capabilities
- Load Balancing: Protocol server load distribution
Performance & Scalability
Performance Characteristics
- Setpoint Calculation: < 100ms per pump
- Protocol Response Time: < 50ms for OPC UA/Modbus
- Database Operations: Optimized connection pooling
- Memory Usage: Efficient caching and resource management
Scalability Features
- Horizontal Scaling: Multiple adapter instances
- Load Distribution: Protocol-specific load balancing
- Resource Optimization: Dynamic resource allocation
- Performance Monitoring: Real-time performance metrics
Integration Patterns
SCADA System Integration
- OPC UA Integration: Standard industrial protocol
- Modbus Integration: Legacy system compatibility
- REST API Integration: Modern web services
- Database Integration: Direct database access
External System Integration
- Alert Systems: Email, SMS, webhook integration
- Monitoring Systems: Health check endpoints
- Security Systems: Integration with enterprise security
- Compliance Systems: Audit log export and reporting
Configuration Management
Configuration Sources
- Environment Variables: Primary configuration method
- Configuration Files: YAML/JSON configuration support
- Database Configuration: Dynamic configuration updates
- Runtime Configuration: Hot-reload capability for certain settings
Key Configuration Areas
- Database Connection: Connection strings and pooling
- Safety Limits: Station and pump-specific safety parameters
- Security Settings: Authentication and authorization configuration
- Protocol Settings: Protocol-specific configuration
- Monitoring Settings: Alert thresholds and monitoring intervals
Development & Testing Architecture
Testing Framework
- Unit Tests: Component-level testing
- Integration Tests: Component interaction testing
- End-to-End Tests: Complete workflow testing
- Deployment Tests: Production environment validation
- Security Tests: Security control validation
Development Workflow
- Code Quality: Linting, type checking, formatting
- Continuous Integration: Automated testing pipeline
- Documentation: Comprehensive documentation generation
- Release Management: Version control and release process
Compliance & Certification
Regulatory Compliance
- IEC 62443: Industrial automation security
- ISO 27001: Information security management
- NIS2 Directive: Network and information systems security
- Industry Standards: Water/wastewater industry standards
Certification Strategy
- Security Certification: IEC 62443 certification process
- Quality Certification: ISO 9001 quality management
- Industry Certification: Water industry-specific certifications
- Continuous Compliance: Ongoing compliance monitoring
This architecture document provides a comprehensive overview of the Calejo Control Adapter system architecture. For detailed implementation specifications, refer to the individual component documentation.